当前位置:首页>日本横河YOKOGAWA

横河ARM15A-000/BR3端子板ARM15A-000/BR3端子板
GENERAL
[Release 5]
This document describes the specifications of relay board used in FIO subsystem of CENTUM VP. Relay input/ output boards are connected in between digital input/output modules (for FIO) and field devices. Relay input boards receive contact signals or voltage input signals of field devices. Relay output boards receive output signals of the digital output module and amplify by the relay, and then output to field devices. These relay boards support dual- redundant digital input/output modules (for FIO).
n STANDARD SPECIFICATIONS
l Relay Boards
Models |
Descriptions |
Contact Points |
Terminals |
Signal Cables |
Connectable Digital I/O Modules |
|
Modules |
Terminal Blocks |
|||||
ARM15A |
Mechanical Relay Board |
32-point |
M4 screws |
AKB331 (for 32-point) |
ADV151 |
ATD5A |
AKB337 (for 64-point) |
ADV161 |
- |
||||
ARM55D |
32-point |
M4 screws |
AKB331 (for 32-point) |
ADV551 |
ATD5A |
|
AKB337 (for 64-point) |
ADV561 |
- |
||||
ARM55W |
32-point |
M4 screws |
AKB331 (for 32-point) |
ADV551 |
ATD5A |
|
AKB337 (for 64-point) |
ADV561 |
- |
||||
ARM55T |
32-point |
M4 screws |
AKB331 (for 32-point) |
ADV551 |
ATD5A |
|
AKB337 (for 64-point) |
ADV561 |
- |
||||
ARM55C |
32-point |
M3.5 screws (M4 in power input part) |
AKB331 (for 32-point) |
ADV551 |
ATD5A |
|
AKB337 (for 64-point) |
ADV561 |
- |
||||
ARS15B-5 (48 V DC) ARS15B-6 (110 V DC) |
Solid State Relay Board |
32-point |
M4 screws |
AKB331 (for 32-point) |
ADV151 |
ATD5A |
AKB337 (for 64-point) |
ADV161 |
- |
||||
ARS15M-1 (100 V AC) ARS15M-2 (220 V AC) ARS15M-3 (10 - 30 V DC) |
32-point |
Pressure clamp terminals |
AKB331 (for 32-point) |
ADV151 |
ATD5A |
|
AKB337 (for 64-point) |
ADV161 |
- |
||||
ARS55M-1 (100 V AC) ARS55M-2 (220 V AC) ARS55M-3 (5 - 60 V DC) |
32-point |
Pressure clamp terminals |
AKB331 (for 32-point) |
ADV551 |
ATD5A |
|
AKB337 (for 64-point) |
ADV561 |
- |
Relay Boards Detail Specifications
Mechanical Relay Boards (Contact Input)
Model |
ARM15A |
Usage |
Mechanical Relay Contact Input (Single / Dual-redundant) |
Contact Points |
32-point |
Terminals for Field Device Connection |
M4 screws |
Modules |
ADV151 (DI: 32-point) + ATD5A (Terminal block) ADV161 (DI: 64-point) (*1) |
Signal Cables |
AKB331 (for 32-point) AKB337 (for 64-point) |
Contact Input Signal |
ON signal: 150 Ω or less OFF signal: At least 200 kΩ |
External Contact Rating (Minimum Load) |
24 V DC, 13 mA (*3) |
Power Supply Voltage and Current Consumption of Internal Circuit (require external power supply) |
24 V DC Max. 0.32 A |
Power Supply for Field Device (require external power supply) |
Dual-line (supply power per 16-point) 24 V DC: Max. 0.3 A per one line |
Insulation Resistance |
At least 10 MΩ (500 V DC) |
Withstanding Voltage |
Between field device terminals and cases: 1.5 kV Between 24 V power terminals and cases: 500 V Between 24 V power terminals and field device terminals: 1.5 kV |
Ambient Temperature and Humidity |
0 to 50 °C, 10 to 90 %RH |
Standards |
EMC standards [CE Marking], [C-Tick Marking], [KC Marking] (*2) |
Size |
W: 482.6 mm x H: 132.5 mm (3U) |
Weight |
2.2 kg |
*1: Two sets of relay board (ARM15A) and two sets of signal cable (AKB337) are required for one ADV161.
*2: ARM15A does not conform to Safety Standard [CSA].
*3: It is voltage/current that ARM15A applies to the external contact power supply.