    ARS55M-210端子板

    类别: 日本横河YOKOGAWA
    发布时间: 2021-03-13 10:28:16
    价格: ¥0
    发送联系信息 订购热线:13530116378
    详情
    横河ARS55M-210端子板ARS55M-210端子板
    Solid State Relay Boards (Voltage Output)

     

    Models

    ARS55M-1 (100 V AC)

    ARS55M-2 (220 V AC)

    ARS55M-3 (5 - 60 V DC)

    Usage

    Solid State Relay TRIAC Output, Transistor output (Single / Dual-redundant)

    Contact Points

    32-point

     

    Terminals for Field Device

    Connection

    Pressure clamp terminals

    Cable specifications: see the table of terminal treatment for the pressure clamp terminal signal line and power line.

     

    Modules

    ADV551 (DO: 32-point) + ATD5A (Terminal block) ADV561 (DO: 64-point) (*1)

     

    Signal Cables

    AKB331 (for 32-point) AKB337 (for 64-point)

     

     

     

     

     

    Output Voltage/Current Range

    (*2)

    24 to 140 V AC

     

    30 mA to 2.5 A

    (Ambient temperature is under

    20 °C)

    30 mA to 2 A (at 20 to 35 °C)

    30 mA to 1.5 A (at 35 to 40 °C)

    30 mA to 1.3 A (at 40 to 50 °C)

     

    Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C.

    24 to 250 V AC

     

    30 mA to 2.5 A

    (Ambient temperature is under

    20 °C)

    30 mA to 2 A (at 20 to 35 °C)

    30 mA to 1.5 A (at 35 to 40 °C)

    30 mA to 1.3 A (at 40 to 50 °C)

     

    Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C.

    5 to 60 V DC

     

    20 mA to 2.5 A

    (Ambient temperature is under 20 °C)

    20 mA to 2 A (at 20 to 35 °C)

    20 mA to 1.3 A (at 35 to 50 °C)

     

     

     

    Inductive load must be 1.5 A or less.

    Power Supply Voltage and Current Consumption of Internal Circuit

    (require external power supply)

     

    24 V DC Max. 0.9 A

    Power Supply for Field Device

    -

    Insulation Resistance

    At least 10 M (500 V DC)

    Withstanding Voltage

    Between 24 V power terminals and field device terminals: 2 kV

    Ambient Temperature and

    Humidity

     

    0 to 50 °C, 10 to 90 %RH

    Standards

    Safety Standard [CSA], EMC standards [CE Marking], [C-Tick Marking] , [KC Marking]

    Size

    W: 436 mm x H: 125.4 mm

    Weight

    3.0 kg

     

    *1:      Two sets of relay board (ARS55M-1, ARS55M-2, or ARS55M-3) and two sets of signal cable (AKB337) are required for one

    ADV561.

    *2:      For inductive loads, connect a spark killer (CR network for AC; diode for DC) in parallel with loads.

     

    Table:  Terminal Treatment for Pressure Clamp Terminal Signal Line

     

     

    Cable Thickness (mm2)

    Peel-off Length (mm)

    Inserting Part of Sleeve (mm)

    Without Sleeves

    0.5 to 2 (AWG20 to 14)

    8

    With Sleeves

    0.5 to 2 (AWG20 to 14)

    8

    8

     

    Table:  Terminal Treatment for Pressure Clamp Terminal Power Line

     

     

    Cable Thickness (mm2)

    Peel-off Length (mm)

    Inserting Part of Sleeve (mm)

    Without Sleeves

    0.5 to 2 (AWG20 to 14)

    9

    With Sleeves

    0.5 to 1.5 (AWG20 to 16)

    9

    8