当前位置:首页>日本横河YOKOGAWA

Solid State Relay Boards (Voltage Output)
Models |
ARS55M-1 (100 V AC) |
ARS55M-2 (220 V AC) |
ARS55M-3 (5 - 60 V DC) |
Usage |
Solid State Relay TRIAC Output, Transistor output (Single / Dual-redundant) |
||
Contact Points |
32-point |
||
Terminals for Field Device Connection |
Pressure clamp terminals Cable specifications: see the table of terminal treatment for the pressure clamp terminal signal line and power line. |
||
Modules |
ADV551 (DO: 32-point) + ATD5A (Terminal block) ADV561 (DO: 64-point) (*1) |
||
Signal Cables |
AKB331 (for 32-point) AKB337 (for 64-point) |
||
Output Voltage/Current Range (*2) |
24 to 140 V AC 30 mA to 2.5 A (Ambient temperature is under 20 °C) 30 mA to 2 A (at 20 to 35 °C) 30 mA to 1.5 A (at 35 to 40 °C) 30 mA to 1.3 A (at 40 to 50 °C) Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C. |
24 to 250 V AC 30 mA to 2.5 A (Ambient temperature is under 20 °C) 30 mA to 2 A (at 20 to 35 °C) 30 mA to 1.5 A (at 35 to 40 °C) 30 mA to 1.3 A (at 40 to 50 °C) Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C. |
5 to 60 V DC 20 mA to 2.5 A (Ambient temperature is under 20 °C) 20 mA to 2 A (at 20 to 35 °C) 20 mA to 1.3 A (at 35 to 50 °C) Inductive load must be 1.5 A or less. |
Power Supply Voltage and Current Consumption of Internal Circuit (require external power supply) |
24 V DC Max. 0.9 A |
||
Power Supply for Field Device |
- |
||
Insulation Resistance |
At least 10 MΩ (500 V DC) |
||
Withstanding Voltage |
Between 24 V power terminals and field device terminals: 2 kV |
||
Ambient Temperature and Humidity |
0 to 50 °C, 10 to 90 %RH |
||
Standards |
Safety Standard [CSA], EMC standards [CE Marking], [C-Tick Marking] , [KC Marking] |
||
Size |
W: 436 mm x H: 125.4 mm |
||
Weight |
3.0 kg |
*1: Two sets of relay board (ARS55M-1, ARS55M-2, or ARS55M-3) and two sets of signal cable (AKB337) are required for one
ADV561.
*2: For inductive loads, connect a spark killer (CR network for AC; diode for DC) in parallel with loads.
Table: Terminal Treatment for Pressure Clamp Terminal Signal Line
Cable Thickness (mm2) |
Peel-off Length (mm) |
Inserting Part of Sleeve (mm) |
|
Without Sleeves |
0.5 to 2 (AWG20 to 14) |
8 |
– |
With Sleeves |
0.5 to 2 (AWG20 to 14) |
8 |
8 |
Table: Terminal Treatment for Pressure Clamp Terminal Power Line
Cable Thickness (mm2) |
Peel-off Length (mm) |
Inserting Part of Sleeve (mm) |
|
Without Sleeves |
0.5 to 2 (AWG20 to 14) |
9 |
– |
With Sleeves |
0.5 to 1.5 (AWG20 to 16) |
9 |
8 |
CENTUM CS在许多工厂中都有实际应用,并具有绝对高的可靠性,自从1993年开始销售以来,CENTUM CS已经成为最畅销的大型DCS。
自从1993年推出以来,CENTUM CS在许多领域的工厂中得到了广泛的应用,如: 石油冶炼,石化,化学,钢铁,有色金属,金属,水泥,造纸,食品和制药,能源,天然气和供水以及许多其他公共应用领域。
CENTUM CS出色的可操作性和工程技术,以及经大量实际应用结果验证的高可靠性,确保其在21世纪继续发挥重要作用。
信息指令站(ICS)
用于操作和监.视工厂过程控制的站点。
控制台式ICS
应用广泛、高度可靠的标准型ICS。
台式ICS
ICS位于桌面上,主机、CRT和键盘是分开的。
PICS
用作ICS的通用PC。
现场控制站(FCS)
用于工厂过程控制的控制单元。
节点
通过远程总线向FCS控制单元传输现场信号的远程输入/输出单元。
工程师站(EWS)
具有工程能力的工作站,用于系统配置和系统维护。
总线转换器(ABC)
如果一个系统包含多个域或保留的CENTUM项目,需要总线转换器。
通讯网关(ACG)
通讯网关单元用于连接监管计算机和控制总线。
V Net
实时控制总线用于连接FCS、ICS和ABC。
E Net
系统的信息LAN,用于连接ICS和EWS。
ARS55M-110横河ARS55M-110端子板