当前位置:首页>日本横河YOKOGAWA

Solid State Relay Boards (Voltage Output)
Models |
ARS55M-1 (100 V AC) |
ARS55M-2 (220 V AC) |
ARS55M-3 (5 - 60 V DC) |
Usage |
Solid State Relay TRIAC Output, Transistor output (Single / Dual-redundant) |
||
Contact Points |
32-point |
||
Terminals for Field Device Connection |
Pressure clamp terminals Cable specifications: see the table of terminal treatment for the pressure clamp terminal signal line and power line. |
||
Modules |
ADV551 (DO: 32-point) + ATD5A (Terminal block) ADV561 (DO: 64-point) (*1) |
||
Signal Cables |
AKB331 (for 32-point) AKB337 (for 64-point) |
||
Output Voltage/Current Range (*2) |
24 to 140 V AC 30 mA to 2.5 A (Ambient temperature is under 20 °C) 30 mA to 2 A (at 20 to 35 °C) 30 mA to 1.5 A (at 35 to 40 °C) 30 mA to 1.3 A (at 40 to 50 °C) Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C. |
24 to 250 V AC 30 mA to 2.5 A (Ambient temperature is under 20 °C) 30 mA to 2 A (at 20 to 35 °C) 30 mA to 1.5 A (at 35 to 40 °C) 30 mA to 1.3 A (at 40 to 50 °C) Inductive load must be 1.5 A or less, even when ambient temperature is under 35 °C. |
5 to 60 V DC 20 mA to 2.5 A (Ambient temperature is under 20 °C) 20 mA to 2 A (at 20 to 35 °C) 20 mA to 1.3 A (at 35 to 50 °C) Inductive load must be 1.5 A or less. |
Power Supply Voltage and Current Consumption of Internal Circuit (require external power supply) |
24 V DC Max. 0.9 A |
||
Power Supply for Field Device |
- |
||
Insulation Resistance |
At least 10 MΩ (500 V DC) |
||
Withstanding Voltage |
Between 24 V power terminals and field device terminals: 2 kV |
||
Ambient Temperature and Humidity |
0 to 50 °C, 10 to 90 %RH |
||
Standards |
Safety Standard [CSA], EMC standards [CE Marking], [C-Tick Marking] , [KC Marking] |
||
Size |
W: 436 mm x H: 125.4 mm |
||
Weight |
3.0 kg |
*1: Two sets of relay board (ARS55M-1, ARS55M-2, or ARS55M-3) and two sets of signal cable (AKB337) are required for one
ADV561.
*2: For inductive loads, connect a spark killer (CR network for AC; diode for DC) in parallel with loads.
Table: Terminal Treatment for Pressure Clamp Terminal Signal Line
Cable Thickness (mm2) |
Peel-off Length (mm) |
Inserting Part of Sleeve (mm) |
|
Without Sleeves |
0.5 to 2 (AWG20 to 14) |
8 |
– |
With Sleeves |
0.5 to 2 (AWG20 to 14) |
8 |
8 |
Table: Terminal Treatment for Pressure Clamp Terminal Power Line
Cable Thickness (mm2) |
Peel-off Length (mm) |
Inserting Part of Sleeve (mm) |
|
Without Sleeves |
0.5 to 2 (AWG20 to 14) |
9 |
– |
With Sleeves |
0.5 to 1.5 (AWG20 to 16) |
9 |
8 |
五、现场数字解决方案
横河电机早期就实现了现场网络在生产控制系统中的潜能,并且在设计系统时引入了现场网路的思想。CENTUM VP支持FF现场总线、HART、PROFIBUS-DP、DeviceNet、Modbus、Modbus/TCP、Ethernet/IP和ISA100.11a无线通信协议。CENTUM VP通过多种通信协议统一控制和监.视各供应商的现场设备。
横河电机的现场数字产品
工厂控制系统中的现场总线应用
现场总线功能模块的工程实施与FCS其他功能模块相同。现场总线功能模块和其他FCS功能模块在操作和监.视环境方面也是相同的。横河电机DCS的现场总线应用在工程、操作和监.视方面没有任何额外的需求。
更多现场总线信息请点击这里。
应用现场总线的最大优势是对现场设备的高效维护。横河电机提供资产管理软件包——工厂资源管理器(PRM),用以进行设备管理和诊断。通过PRM,现场总线的优势得以优化,使得整个系统的维护更加高效。
工厂资源管理器(PRM)
PRM通过现场总线收集设备维护信息,将其存储在PRM数据库中。通过现场总线即可进行现场设备的维护。因此维护工程师无需深入偏远地区和危险区域的设备现场,工作效率得到了极大的提高。
审计跟踪
审计跟踪管理在控制和维护系统中是非常重要的。所有由PRM进行的设备维护工作都会被记录和存储下来,检索起来也非常方便。
预见性维护
通过设备管理信息的综合管理,可以预测设备的更新周期和设备故障的发展趋势。这种技术可最小化设备问题对工厂运行的影响,也可以计划和安排维护工作以及零件的采购。
非现场总线设备的解决方案
除现场总线设备外,PRM也可以为已有设备创建数据库。数据库中记录并管理维护信息,以支持工厂中所有设备的整体全面的计划维护。
六、控制网络
Vnet/IP——世界上最快的开放式控制网络
横河电机已经开发了Vnet/IP开放式网络协议,可以提供开放、可靠和实时的宽带通信。CENTUM和非CENTUM组件都可连接到网络。Vnet/IP协议获准为IEC 61784-2 Ed.2.0标准,并且符合IEEE 802.3和UDP/IP。
更多Vnet/IP信息请点击这里。
抵抗网络攻击的鲁棒性
横河电机的AFV10D 控制器、AFV30D控制器和AVR10D V net路由器已经如期通过了Wurldtech安全技术公司的Achilles I级测试,确保控制器的终端安全。
网络交换机
横河电机已经和百通公司达成了协议,后者全权负责用于Vnet/IP的高可靠、高性能的赫斯曼网络交换机的供应与维护。
这些交换机有助于建立可靠的工厂网络,而且通过在产品上印记双标识,横河电机将确保长期的维护支持。
ARS55M-310端子板