当前位置:首页>日本横河YOKOGAWA

横河ALR111-S50通信模块ALR111-S50通信模块
HARDWARE SPECIFICATIONS
The serial communication modules (ALR111 and ALR121) hardware specifications are as shown below.
Table Serial Communication Module Hardware Specifications
Item |
Specifications |
|
Model |
ALR111 |
ALR121 |
Interface |
RS-232C |
RS-422/RS-485 |
Connection method |
Point-to-point |
Point-to-point (RS-422) Multipoint (RS-485) |
Communication function |
Half-duplex |
|
Synchronization method |
Start-stop synchronization |
|
Transmission speed |
1200/2400/4800/9600/19200/38400 bps (*1) |
|
Transmission code |
ASCII/binary |
|
Character length |
7/8 bits |
|
Stop bit length |
1/2 bits |
|
Parity check |
None/even/odd |
|
Lag time after data transmission |
1 ms (The lag time to start receiving data again after data transmission.) |
|
Transmission distance |
Maximum 15 m |
Maximum 1200 m (total extended length) |
Installation method |
Mounted on ANB10£, ANB11£, ANR10£, AFF50£, AFV10£, AFV30£, or AFV40£ |
|
I/O wiring |
AKB131, AKB132, AKB133, AKB134 cables, etc. |
Cable with 3-pair shield, AKB161, or AKB162 |
Wiring connection |
D-sub-9-pin (female x 2) |
Clamped with terminal block’s M4 screws (5 poles x 2) |
Current consumption |
0.5A |
|
Weight |
0.3 kg |
0.3 kg |
*1: The applicable transmission speed depends on the communication function, subsystems, and connection method.
An FCS collects data from subsystems or sets data with control calculations to subsystems using the builder functions by way of serial communication modules. A communication module selects only one communication function, thus
two ports must have identical communication functions. It is not possible to select different communication function for every port. The communication functions and those transmission speeds for each communication module are as shown in the table below.
Table Communication Functions for Communication Modules
Communication function |
ALR111 |
ALR121 |
FA-M3 communication |
DR |
DR |
Modbus communication |
DR |
DR |
MELSEC-A communication |
DR |
DR |
YS communication with direct connection |
NIL |
SG |
YS communication |
NIL |
SG |
SLC500 communication |
SG |
SG |