TC Input/RTD Input Module (Isolated Channels)
These modules receive signals from mV, thermocouple (TC), RTD, and potentiometer (POT). These are isolated between the field and the system as well as between each channel.
They can be used in dual redundant configuration.
These two modules can be used in dual redundant configuration.
Items |
Specifications |
||
Model |
AAT145 |
AAR145 |
|
Number of input channels |
16, isolated channels |
16, isolated channels |
|
Input signal |
TC: JIS C1602:1995 (*1), IEC584:1995 Type J, K, E, B (*2), R, S, T, N mV: -100 to 150 mV, -20 to 80 mV |
RTD: JIS C1604:1997 (*3), IEC751:1995 Pt100 (3-wire type) POT: Total resistance 100 Ω to 10 kΩ Span resistance: 50 % or more of total resistance |
|
Switching input signals |
TC/mV can be set individually for CH1 to CH16. |
RTD/POT can be selected individually for CH1 to CH16. |
|
Allowable input voltage |
±5 V |
±5 V |
|
Withstanding voltage |
Between input and system: 500 V AC (for single card: 1500 V AC), For 1 minute Between input channels: 200 V AC, For 1 minute |
||
Input resistance |
Power ON |
1 MΩ or more |
|
Power OFF |
1 MΩ or more |
||
Accuracy |
±40 µV |
RTD: ±150 mΩ POT: ±0.2 %/FS |
|
Allowable total resistance of signal source plus wiring |
1000 Ω or less |
150 Ω or less (wiring resistance per wire)(*4) |
|
Effect of allowable signal source resistance (1000 Ω) |
±20 µV |
— |
|
Reference junction compensation accuracy |
±1 °C (*5) (6) |
— |
|
Measurement current |
— |
RTD: 1 mA |
|
Data update period |
1 s |
||
Burn-out |
All channels can be set together. Setting: not available/available (UP/DOWN) detection time: 60 s |
||
Temperature drift |
±80 µV/10 °C |
RTD: ±0.3 Ω/10 °C POT: ±0.4 %/10 °C |
|
Maximum current consumption |
350 mA (5 V DC) |
350 mA (5 V DC) |
|
Weight |
0.3 kg |
||
External connection |
Dedicated cable (KS1) |
Dedicated cable (KS8/AKB335) |
*1: Model AAT145 is also in compliance with JIS C1602:1981.
*2: Type B dose not carry out temperature compensation and can not measure under 44 °C.
*3: Model AAR145 is also in compliance with JIS C1604:1989 (Pt100, JPt100).
*4: Wiring resistance for the signal cables of IN£A and IN£B must be identical.
*5: This accuracy changes due to the installation condition.
If measured temperature is lower than 0 °C, multiply the above value by the following coefficient (K):
Thermoelectromotive force per degree at 0 °C
Thermoelectromotive force per degree at measured temperature
F05E.ai
*6: Reference junction compensation accuracy varies depending on the temperature environment of terminal board (AET4D).
Specifications for Terminal board only
Temperature Environment |
Reference Junction Compensation accuracy |
-20 to 0 ˚C |
±1.5 ˚C |
0 to 30 ˚C |
±1.0 ˚C |
30 to 70 ˚C |
±1.5 ˚C |
Specifications for installing in a standard cabinet
Temperature Environment |
Reference Junction Compensation accuracy |
0 to 30 ˚C |
±1.0 ˚C |
30 to 50 ˚C |
±1.5 ˚C |