当前位置:首页>日本横河YOKOGAWA

AAM10 电流/电压输入模块
Current/Voltage Input Module (Simplified Type)
This module receives 4-20 mA from 2-wire transmitters and 1-5 V standardized signals.
Items |
Specifications |
|
Model |
AAM10 |
|
Input signal |
1 to 5 V DC |
4 to 20 mA DC (*1) (*2) (It is possible to supply power to a transmitter) |
Input resistance |
1 MΩ at power-up (100 kΩ at power-down) |
250 Ω |
Allowable input voltage/current |
-10 to 30 V DC |
40 mA DC or less |
Transmitter power supply |
- |
25.0 to 25.5 V DC (Output current limit: 60 mA DC or less ) |
Auxiliary voltage output |
None |
|
Square root extraction |
None |
|
Accuracy |
Voltage input: ±4 mV; Current input: ±16 mA |
|
Effect of ambient temperature change |
For 10 °C change: Voltage input: ±8 mV Current input: ±32 µA |
|
Data update period |
50 ms |
|
Current consumption |
250 mA or less (5.0 V DC) |
|
Signal isolation |
Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min |
|
How installed |
Installed in the I/O Module Nest. |
|
How connected |
Connected to the terminals of the I/O Module Nest with M4 screws. |
|
How input signals are specified |
Specify input signals and range by software setting. |
*1: This module can be combined with MTL barrier 728. At this time, wiring resistance must be 10 Ω or less and the lowest operating voltage of the 2-wire transmitter must be 12 V DC or less.
*2: When the power of AAM10 is OFF or an abnormal condition occurs, the current input loop is open.
Do not share current signals with other receivers. To share signal, attach Shunt Resistance (250 Ω) to current-output module and share voltage output.
DCS培训资料:
双重化FCU的结构
表3.2 FCU的硬件规格
FCU功能类型 组成卡件 |
标准型 |
扩展型 |
说 明 |
|
处理器卡 |
CPU |
RISI处理器 |
||
主存贮容量 |
8MB |
16MB |
带ECC(注1) |
|
V net接口 |
单通道或双重化冗余 |
|||
节点通讯卡 |
RIO总线数 |
1 |
||
冗余方式 |
单片或双重化冗余 |
|||
I/O点数 |
1280模拟信号或4096结点信号 |
见FCS应用容量 |
(注1)ECC:纠错码(Error Correcting Code)